A6000 Digital panel meter
A6000 Digital panel meter Features Common Specification Input Specification Output Specification
Features Common Specification Input Specification Output Specification
Power supply 100 to 240V AC 12 to 48V DC Panel cut out 96mm(W) x 48mm(H). Option BCD output, RS-232C, RS-485. HI, GO, LO 2 setpoints, Analog output. Input DC, AC, TC, RTD, Frequency, Stain Gauge, Resistance.
Common specification
Display
Main display: Red or Green LED 20mm Sub display: Red LED 6mm
Conversion rate
1000 times/sec/
Maximum display
9999
Over range indication
When input exceeds the maximum display OVER or -OVER
Zero display
Leading zero suppression
Decimal points
Settable to any digit position
Operation temperature
0 to 50°C, 35 to 85% RH
Storage temperature
-10 to 70°C less than 60% RH
Power supply
AC 100 to 240Vac ±10% DC 12 to 48V ±10%
Power consumption
8VA (max. load)
Dimensions
96mm (W) x 48mm (H) x 147.5mm (D) DIN size
Weight
Approx.. 450g
Dielectric strength (AC)
Power supply/ input terminal/ output terminal AC1500V/1 min.
Dielectric strength (DC)
Power supply/ input terminal/ output terminal DC5000V/1 min.
Dielectric strength (Common)
Case/power supply/Input terminal output terminal AC2000V/1 min.
Insulation resistance
DC 500V, more than 100MΩ the above terminals.
Input specification
1
DC Voltage
2
DC current
3
DC Current
4
AC voltage
5
AC current
6
7
Resistance
8
Temperature (T/C, RTD)
9
Frequency
A
Stain Gauge
B
Process
Output specification
0
None
External control
BCD output (TTL)
BCD output (Open collector)
Analog output
RS-232C
RS-485
RS-232C + analog output
RS-485 + analog output